Technical
Function:
Over- and undervoltage monitoring
Interrupted neutral monitoring
Over- and underfrequency monitoring
10 minutes average value monitoring
Vector shift detection
ROCOF monitoring
Measuring Range:
0 … 540 V AC
Rated Control Supply Voltage (U s ):
24 … 240V AC/DC
Exit:
3 c/o (SPDT) contacts
Terminal Type:
Screw Terminals
Rated Operational Current AC-12 (I e ):
(230V) 4A
Rated Operational Current AC-15 (I e ):
(230V) 3A
Rated Operational Current DC-12 (I e ):
(24V) 4A
Rated Operational Current DC-13 (I e ):
(24V) 2A
Minimum Switching Capacity:
24V
10mA
Degree of Protection:
Housing IP20
Terminals IP20
Pollution Degree:
3
Short Circuit Protective Devices:
Output Circuit NC – F Type Fuses 10 A
Output Circuit NO – F Type Fuses 10 A
Electrical Durability:
AC-12 50000 cycle
Mechanical Durability:
30000000 cycle
Connecting Capacity:
Flexible with Ferrule 1x 0.25 … 4.0 mm²
Flexible with Ferrule 2x 0.25 … 0.75 mm²
Flexible with Insulated Ferrule 1x 0.25 … 4.0 mm²
Flexible with Insulated Ferrule 2x 0.25 … 0.75 mm²
Flexible 1x 0.2 … 4.0 mm²
Flexible 2x 0.2 … 1.5 mm²
Rigid 1x 0.2 … 6.0 mm²
Rigid 2x 0.2 … 1.5 mm²
Tightening Torque:
0.5 … 0.6 N m
Wire Stripping Length:
8mm
Mounting Position:
1 … 6
DIN Rail Mounting:
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Standards:
VDE-AR-N 4105
VDE-AR-N 4110
VDE-AR-N 4120