Eaton Contactor 380 V 400 V 110 kW Screw connection DILM225

Contactor

Description
DILM225A/22(RDC24) - Contactor, 380 V 400 V 110 kW, 2 N/O, 2 NC, RDC 24: 24 - 27 V DC, DC operation, Screw connection
DILM225A/22(RDC24) Y7-139550
DILM225A/22(RDC130) Y7-139552
DILM25-10-EA(RDC24) Y7-189914
DILM25-10(RDC130) Y7-277148
DILM25-01-EA(RDC24) Y7-189916
DILM25-01(RDC130) Y7-277180

Product name
Eaton Moeller® series DILM Contactor
Part no.
DILM225A/22(RDC24)
EAN
4015081363285
Product Length/Depth
158 millimetre
Product height
190 millimetre
Product width
140 millimetre
Product weight
3.54 kilogram
Certifications
CSA Class No.: 3211-04
IEC/EN 60947
UL Category Control No.: NLDX
CSA
CSA-C22.2 No. 60947-4-1-14
IEC/EN 60947-4-1
UL
CE
VDE 0660
UL 60947-4-1
CSA File No.: 2389068
UL File No.: E29096
Product Tradename
DILM
Product Type
Contactor
Product Sub Type
None
Catalog Notes
Conventional thermal current Ith of main contacts (1-pole, open) at 60°
Also suitable for motors with efficiency class IE3.
Also tested according to AC-3e up to 500 V.
Contacts according to EN 50012
General information
Accessories
Fitting options auxiliary contacts: on the side: 2 x DILM1000-XHI(V)11-SI; 2 x DILM1000-XHI11-SA
Application
Contactors for Motors
Connection
Screw terminals
Degree of protection
IP00
Electromagnetic compatibility
Designed for operation in industrial environments. Its use in residential environments may cause radio-frequency interference, requiring additional noise suppression.
Fitted with:
Suppressor circuit in actuating electronics
Lifespan, electrical
100,000 Operations (at Condensor operation)
Lifespan, mechanical
10,000,000 Operations (DC operated)
Operating frequency
200 Operations/h
3000 mechanical Operations/h (DC operated)
Overvoltage category
III
Pollution degree
3
Product category
Contactors
Protection
Finger and back-of-hand proof with terminal shroud or terminal block, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)
8000 V AC
Shock resistance
8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Utilization category
AC-3: Normal AC induction motors: starting, switch off during running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Voltage type
DC
Category: