ABB AUTOMATIC TRANSFER SWITCH (ATS)

ATS

Description
2P 63 230:220-240 OTM63F2C20D230C 1SCA151421R1001 
2P 125 230:220-240 OTM125F2C20D230C 1SCA151417R1001 
3P 63 400:380-415 OTM63F3C20D400C 1SCA151423R1001
3P 125 400:380-415 OTM125F3C20D400C 1SCA151419R1001
4P 40 400:380-415 OTM40F4C20D400C 1SCA151252R1001
4P 63 400:380-415 OTM63F4C20D400C 1SCA151254R1001
4P 125 400:380-415 OTM125F4C20D400C 1SCA151250R1001
2P 63 230:220-240 OTM63F2C21D230C 1SCA151422R1001 
2P 125 230:220-240 OTM125F2C21D230C 1SCA151418R1001 
3P 63 400:380-415 OTM63F3C21D400C 1SCA151424R1001 
3P 125 400:380-415 OTM125F3C21D400C 1SCA151420R1001 
4P 40 400:380-415 OTM40F4C21D400C 1SCA151253R1001 
4P 63 400:380-415 OTM63F4C21D400C 1SCA151255R1001 
4P 125 400:380-415 OTM125F4C21D400C 1SCA151251R1001
Technical
Rated Operational Current AC-21A (I e ):
(380 … 415 V) 125 A

Rated Operational Current AC-22A (I e ):
(380 … 415 V) 125 A

Rated Operational Current AC-23A (I e ):
(380 … 415 V) 90 A

Rated Operational Current AC-31B (I e ):
(380 … 415 V) 125 A

Rated Operational Current AC-32B (I e ):
(380 … 415 V) 125 A

Rated Operational Current AC-33B (I e ):
(380 … 415 V) 80 A

Rated Operational Power AC-23A (P e ):
(380 … 415V) 45kW

Conventional Free-air Thermal Current (I th ):
Θ = 40 °C 125 A

Rated Impulse Withstand Voltage (U imp ):
8 kV

Rated Insulation Voltage (U i ):
800V

Nominal Working Voltage:
Main Circuit 380…415V

Rated Short-time Withstand Current Low Voltage (I cw ):
for 1 s 2.5 kiloampere rms

Motor Operational Voltage:
380…415V AC

Power Loss:
at Rated Operating Conditions per Pole 6.3 W

Pollution Degree:
3

Handle Type:
Direct mounted handle

Fourth Pole Type:
Switched – Simultaneous Function

Position of Line Terminals:
Supplies on Top – Load on Bottom

Controller Type:
20D

Mounting Type:
Base Mounting Or DIN-rail mounting

Number of Poles:
4

Degree of Protection:
Front IP20

Terminal Type:
Screw Terminals

Tightening Torque:
acc. IEC 60947-1 6 N m
Transition Type:
Open