Product range
ETR4 timing relays
Basic function
Timer relays
Function
Multi-functional
On-delayed
Off-delayed
Fleeting contact on energization
Fleeting contact on de-energization
Flashing, pulse initiating
On- and Off-delayed
Pulse forming
Pulse generating
On-delayed
Off-delayed
Fleeting contact on energization
Fleeting contact on de-energization
Flashing, pulse initiating
On- and Off-delayed
Pulse forming
Pulse generating
With potentiometer connection (10 kΩ)
Changeover contact can be converted to 2 timed contacts or 1 non-delayed contact and 1 timed contact
Adjustable timing functions
Changeover contact can be converted to 2 timed contacts or 1 non-delayed contact and 1 timed contact
Adjustable timing functions
Number of changeover contacts
2
Time range
0.05 s – 100 h
Time range
0.05 – 1 s
0.15 – 3 s
0.5 – 10 s
1.5 – 30 s
5 – 100 s
15 – 300 s
1.5 – 30 min
15 – 300 min
1.5 – 30 h
5 – 100 h
0.15 – 3 s
0.5 – 10 s
1.5 – 30 s
5 – 100 s
15 – 300 s
1.5 – 30 min
15 – 300 min
1.5 – 30 h
5 – 100 h
Rated operational current [Ie]
AC-14 [Ie]300 V [Ie ]
3 A
AC-14 [Ie]380 V 400 V 415 V [Ie ]
3 A
AC-14 [Ie]
Value applies starting with release 001.
AC-15220 V 230 V 240 V [Ie]
3 A
AC-15300 V [Ie]
3 A
AC-15380 V 400 V 415 V [Ie]
3 A
AC-15
Value applies starting with release 001.
Voltage range [ULN]
24 – 240 V AC, 50/60 Hz
24 – 240 V DC V
24 – 240 V DC V
Width
22.5 mm
TECHNICAL DATA
General
Standards
Standard IEC/EN 61812
VDE 0435
VDE 0435
Lifespan, mechanicalAC operated [Operations]
30 x 106
Lifespan, mechanicalDC operated [Operations]
30 x 106
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureAmbient temperature, storage
– 45 – + 85 °C
Ambient temperatureOpen
-25 – +60 °C
Ambient temperatureEnclosed
– 25 – + 45 °C
Mounting position
As required
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 20 msMake contact
4 g
Degree of protectionTerminals
IP20
Weight
0.1 kg
Terminal capacitiesSolid
1 x (0.5 – 2.5)
2 x (0.5 – 1.5) mm2
2 x (0.5 – 1.5) mm2
Terminal capacitiesFlexible with ferrule
1 x (0.5 – 2.5)
2 x (0.5 – 1.5) mm2
2 x (0.5 – 1.5) mm2
Terminal capacitiesSolid or stranded
1 x (20 – 14) AWG
Contacts
Rated impulse withstand voltage [Uimp]
4000 V AC
Rated impulse withstand voltage [Uimp]
6000 V AC
Value applies starting with release 001.
Overvoltage category/pollution degree
III/2
Rated insulation voltage [Ui]
400 V AC
Rated insulation voltage [Ui]
600 V AC
Value applies starting with release 001.
Rated operational voltage [Ue]
300 V AC
Rated operational voltage [Ue]
440 V AC
Value applies starting with release 001.
Safe isolation to EN 61140between coil and auxiliary contacts
250 V AC
Safe isolation to EN 61140between the auxiliary contacts
250 V AC
Making capacityAC-14 cos ϕ = 0.3 400 V
48 A
Making capacityAC-15 cos ϕ = 0.3 220 V
50 A
Making capacityDC-11 L/R – 40 ms
1.1 x Ie
Breaking capacityAC-14 cos ϕ = 0.3 440 V
3 A
Breaking capacityAC-15 cos ϕ = 0.3 220 V
3 A
Breaking capacityDC-11 L/R – 40 ms
1.1 x Ie
Rated operational current [Ie ]AC-14 [Ie]380 V 400 V 415 V [Ie ]
3 A
Rated operational current [Ie ]AC-14 [Ie]
Value applies starting with release 001.
Rated operational current [Ie ]AC–14440 V [Ie ]
3 A
Rated operational current [Ie ]AC-15220 V 230 V 240 V [Ie]
3 A
Rated operational current [Ie ]DC-11Note
Making and breaking conditions to DC13, time constant as stated
Rated operational current [Ie ]DC-11L/R max. 15 ms24 V [Ie ]
1.5 A
Rated operational current [Ie ]DC-11L/R max. 50 ms
1.2 A
Conv. thermal current [Ith]
6 A
Short-circuit rating without weldingNote
When supplied directly from mains or transformer > 1000 VA
Short-circuit rating without weldingMax. fuse, make contacts
6 A gG/gL
Short-circuit rating without weldingMax. fuse, break contacts
6 A gG/gL
Short-circuit rating without weldingMax. overcurrent protective device, 220/230 V
FAZ-B4/1-HI Type
Magnet systems
Power consumptionPick-up AC
2 VA
Power consumptionSealing AC
2 VA
Power consumptionPick-up DC
1.8 W
Power consumptionSealing DC
1.8 W
Duty factor
100 % DF
Maximum operating frequency
4000 Ops/h
Minimum command timeAC
50 ms
Minimum command timeDC
30 ms
Repetition accuracy (deviation)
≦ 0.5 %
Recovery time (after 100% time delay)
70 ms
Contact changeover time [tu ]
4 ms
Electromagnetic compatibility (EMC)
Electrostatic discharge (ESD)applied standard
IEC/EN 61000-4-2
Electrostatic discharge (ESD)Air discharge
8 kV
Electrostatic discharge (ESD)Contact discharge
6 kV
Electromagnetic fields (RFI)applied standard
IEC/EN 61000-4-3
Electromagnetic fields (RFI)
80 – 1000 MHz: 10
1.4 – 2 GHz: 3
2.0 – 2.7 GHz: 1 V/m
1.4 – 2 GHz: 3
2.0 – 2.7 GHz: 1 V/m
Radio interference suppression
EN 55011, Class B (conducted)
EN 55011, Class B (radiated)
EN 55011, Class B (radiated)
Burst
Supply cables: 2
Signal cables: 1
according to IEC/EN 61000-4-4 kV
Signal cables: 1
according to IEC/EN 61000-4-4 kV
power pulses (Surge)
2 kV (symmetrical)
4 kV (asymmetrical)
according to IEC/EN 61000-4-5
4 kV (asymmetrical)
according to IEC/EN 61000-4-5
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
DESIGN VERIFICATION AS PER IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation [In]
6 A
Heat dissipation per pole, current-dependent [Pvid]
1.4 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
1.8 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+60 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard’s requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard’s requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard’s requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard’s requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard’s requirements.
10.2 Strength of materials and parts10.2.5 Lifting
10.7 Internal electrical circuits and connections
Is the panel builder’s responsibility.
10.8 Connections for external conductors
Is the panel builder’s responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder’s responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder’s responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder’s responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.